Synchronous compensators: models verified by tests of automatic voltage regulator, reactive power control, and voltage joint control

This paper presents models verified by tesis of the excitation control systems (ECSs) of six large synchronous compensators (SCs) rated +125/-120 MVAr. These equipments for grid voltage control are placed in the substation Ezeiza of 500 kV belonging to the Interconnected Argentine System (SADI in Sp...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: Agüero, Jorge Luis, Arnera, Patricia Liliana, Bianchi Lastra, Raúl E., Beroqui, Mario César
Formato: Articulo
Lenguaje:Inglés
Publicado: 2006
Materias:
Acceso en línea:http://sedici.unlp.edu.ar/handle/10915/37083
https://app.box.com/s/1j57cca1hmuybb53n1n1ls74hj7arxys
Aporte de:
Descripción
Sumario:This paper presents models verified by tesis of the excitation control systems (ECSs) of six large synchronous compensators (SCs) rated +125/-120 MVAr. These equipments for grid voltage control are placed in the substation Ezeiza of 500 kV belonging to the Interconnected Argentine System (SADI in Spanish). The substation Ezeiza is located in the SADI load center. Each SC has an ECS integrated by an automatic voltage regulator (AVR) with several limiters and a reactive power control (RPC). ECSs are governed by a single voltage joint control (VJC) to control the voltage at a 500-kV bus bar. The ECS is UNITROL F from ABB and the VJC is implemented in a programmable logic controller (PLC). The AVR, RPC and VJC models are presented. These models were predefined with information furnished by the manufacturer. Then, these models were validated by tests. Test records and their simulations with the proposed model are also presented. Described models have been incorporated to the database of dynamic models used for stability studies in the SADI.